Answer by ThreePhaseEel for Sub Panel using Sub Feed Lugs

Your panel's limit on stab ampacity only applies to double-stuff breakers Your panel's label should read, among other things: SUM OF QT BREAKER RATING IS NOT TO EXCEED 110A PER BRANCH CIRCUIT BUS STAB...

View Article



Answer by Harper for Sub Panel using Sub Feed Lugs

Your subfeed lugs will be downstream of a 200A breaker. So the wire run out to the garage will be protected by a 200A breaker. "Oh, but it will also be protected by the small load since I'll never draw...

View Article

Answer by Paul Logan for Sub Panel using Sub Feed Lugs

You are making this way too difficult. Please, let's just start with what kind of load you would like to be able support in the new garage. Then we can figure out the best way to carry the load and the...

View Article

Sub Panel using Sub Feed Lugs

We're getting ready to build a detached garage/ADU about 100' from our main house, and have a quick question about getting power out to the building. We currently have a 320amp service to the main...

View Article